What fugitive emissions are
They are small leaks of process fluid through the stem seal and the body joints of a valve. One valve leaks very little, but in a plant with thousands of valves the leaks become an environmental and safety issue. That is why many oil & gas and chemical specifications require valves qualified to ISO 15848-1 or API 624 / API 641.
The three classes in the standard
The result of an ISO 15848-1 qualification is expressed with three classes:
Tightness class
AH, BH, CH when the test uses helium; AM, BM, CM when it uses methane. A is the tightest class, typical of bellows seals; B and C are common for packed stems. With helium the leak rate is expressed in mbar·l/s per mm of stem diameter, with methane in ppmv measured by sniffing.
Endurance class
Number of mechanical open-close cycles performed during the test, together with thermal cycles: CO1, CO2, CO3 for isolating (on-off) valves, CC1, CC2, CC3 for control valves, which work with many more cycles.
Temperature class
The test is run at room temperature and at the declared temperatures, for example t(-46 °C) or t(200 °C). The qualification covers the range between the tested temperatures.
ISO 15848-1, ISO 15848-2 and API 624 / 641
A practical summary. The text of the standard in the edition named in the order always prevails.
| Aspect | ISO 15848-1 | ISO 15848-2 | API 624 / API 641 |
|---|---|---|---|
| Type of test | Type test: qualifies a valve design | Production test on the valves supplied | Type test: API 624 for rising-stem valves with graphite packing, API 641 for quarter-turn valves |
| Test fluid | Helium or methane | Helium | Methane |
| Cycles and temperature | Mechanical and thermal cycles according to the endurance and temperature classes | No cycles, at room temperature | Mechanical and thermal cycles defined in the standard |
| Acceptance | Tightness class achieved (AH…CH or AM…CM) | Production class required by the order | Limit in ppmv set by the standard |
A type test qualifies a design (valve type, size and pressure-class range, sealing system); it does not replace a production test on the valves you buy.
How to read the designation
An ISO 15848-1 certificate shows a designation such as “ISO FE BH – CO1 – SSA1 – t(RT, 200 °C) – CL300 – ISO 15848-1”: tightness class BH with helium, endurance class CO1, one stem seal adjustment allowed, tested at room temperature and at 200 °C, pressure class 300. Before accepting it, check that the certificate really covers the valve you are buying: type, stem diameter, pressure class, temperature and, above all, the same sealing system and packing.
What the inspector checks during the test
A checklist to use when witnessing a helium test. Adapt it to the approved procedure.
1. Before the test
- Approved test procedure with required classes, pressure, temperatures and measuring points
- Valve identified; packing or seal of the same type and manufacturer stated in the procedure
- Helium leak detector (mass spectrometer) calibrated, and calibrated reference leak with a valid certificate
- Pressure gauges and thermocouples calibrated, with a suitable range
2. During the measurement
- Helium background measured and recorded before the test
- Detector checked against the reference leak before and after the measurements
- Method and probe position as per procedure (enclosure on the stuffing box, or probe at the body seals)
- Values recorded in the correct units, with the stem diameter used for the calculation
3. During the cycles (type test)
- Mechanical cycles counted and recorded
- Thermal cycle temperatures recorded
- Every stem seal adjustment recorded and compared with the SSA class
4. Report
- Measured leak rates for each point and stage, class achieved compared with the class required
- Serial numbers of detector, reference leak and instruments; photos of the test
The non-conformities we find most often
- Detector not checked against the reference leak before measuring
- High helium background in the test area, not recorded
- Packing different from the one in the qualification
- Stem seal adjustments not recorded, or more than the SSA class allows
- Type-test certificate presented for a valve it does not cover (different size, class or temperature)
Our experience
We have witnessed fugitive emission tests with helium and a mass-spectrometer leak detector on control valves at the Baker Hughes – Nuovo Pignone plant in Bari. The report records measured values, instruments, photos and, when everything conforms, the Inspection Release Note.